Acceptance Standards for Visual Weld Inspection as per B31.1

Visual Examination B31.1 — Acceptance Criteria | WeldFabWorld

Visual Examination as per ASME B31.1 — Acceptance Criteria for Power Piping Welds (Para. 136.4.2)

By WeldFabWorld Published: February 21, 2025 Updated: September 4, 2025 10 min read

Visual examination under ASME B31.1 — the Power Piping Code — is the mandatory baseline inspection method applied to every completed weld in a power piping system, regardless of the additional radiographic or ultrasonic examination requirements that may also apply. Paragraph 136.4.2 of the 2022 edition sets out the specific acceptance and rejection criteria that an examiner must apply when evaluating the external surface condition of butt welds, fillet welds, and branch connection welds in steam, boiler feed water, blowdown, and related high-pressure, high-temperature service piping.

Power piping operates in some of the most demanding service conditions encountered in engineering practice. Steam supply lines to turbines, main steam headers, and reheater piping routinely carry steam at temperatures exceeding 540 °C and pressures above 16 MPa. In this environment, even small surface discontinuities that would be conditionally acceptable in ambient-temperature process piping under ASME B31.3 can become initiation sites for creep cracking, fatigue failure, or stress corrosion over the life of the plant. The stricter acceptance criteria in B31.1 reflect this reality.

This guide explains the complete visual examination framework for B31.1 welds: the scope of Chapter VI, the procedural basis from ASME BPVC Section V Article 9, every acceptance and rejection criterion in Paragraph 136.4.2 with quantitative limits, the weld reinforcement limit table, the specific treatment of longitudinal versus circumferential welds, practical guidance for inspectors, and a comparison with B31.3 criteria where instructive. Practice your code knowledge with the ASME Section IX quiz and ASME Section VIII Division 1 quiz on WeldFabWorld.

Code edition note: This article references ASME B31.1-2022. The core visual examination acceptance criteria of Paragraph 136.4.2 have been stable across recent editions, but always verify the specific edition called for in your project specification or engineering design before applying any code limit.

ASME B31.1 Chapter VI — Inspection, Examination, and Testing Framework

Chapter VI of ASME B31.1 is titled “Inspection, Examination, and Testing” and establishes the complete quality assurance framework for verifying weld quality in power piping fabrication and installation. Understanding the structure of this chapter is essential before interpreting the specific criteria of Paragraph 136.4.2, because the code draws a deliberate and important distinction between inspection and examination.

Inspection vs. Examination — The Critical Distinction

Under B31.1, inspection refers to activities performed by the Owner’s Authorised Inspector (AI) — typically a third-party inspector employed by an insurance company or inspection body. The AI verifies that the fabricator’s quality programme is functioning and that the piping has been constructed in conformance with the code and the engineering design. The AI has the right of access to all stages of manufacture and fabrication.

Examination, by contrast, refers to specific quality control activities performed by the fabricator’s or installer’s own qualified personnel — visual examination, radiography, ultrasonic testing, liquid penetrant, and magnetic particle testing. Paragraph 136 governs examination requirements; Paragraph 137 governs inspection requirements for the Owner’s AI.

Table 136.4 — Extent of Required Examination

Not all welds in a B31.1 system require the same examination scope. Table 136.4 of the code specifies the minimum required extent of examination for different types of joints and different service conditions. The key provisions are:

Weld Type and Service Condition Visual Examination Radiography (RT) Notes
All butt welds — all P-No. materials 100% See RT column VT is mandatory for every completed butt weld regardless of RT requirement
High-temperature / high-pressure service (above 750 °F or above 350 °F at >1025 psi, NPS >2, wall >3/4 in.) 100% 100% Both VT and RT required; RT does not substitute for VT
Other butt welds not meeting the above pressure/temperature threshold 100% Not required by code alone Project specification may add RT requirement
Socket welds and fillet welds 100% Not applicable VT only; RT is not practicable for fillet geometry
In-process examination (fit-up, root pass) Required N/A Fit-up and root pass examination by someone other than the welder is good practice and often project-required
Code reference: ASME B31.1-2022, Table 136.4 — “Extent of Required Examination.” Visual examination of all welds is the minimum examination requirement under the code. Projects operating under additional codes (ASME Section I for boilers, or applicable state or national regulations) may impose additional requirements beyond Table 136.4.

Visual Examination Procedure — ASME BPVC Section V, Article 9

Paragraph 136.4.2 of B31.1 requires that visual examination be performed in accordance with the guidelines outlined in ASME BPVC Section V, Article 9. Article 9 defines the procedural requirements for visual examination in ASME pressure equipment work, covering illumination levels, distance and angle requirements, optical aids, and written procedure requirements.

Key Article 9 Procedural Requirements

  • Illumination: A minimum of 1,000 lux (approximately 100 foot-candles) of white light at the examination surface. In confined or poorly lit areas, supplemental lighting or a portable lamp must be used.
  • Distance and angle: The examiner’s eye must be within 600 mm (24 in.) of the examination surface, and the line of sight must not be less than 30 degrees to the surface being examined.
  • Optical aids: Mirrors, magnifiers, borescopes, and cameras may be used to gain access to surfaces that cannot be directly viewed within the above distance and angle limits.
  • Written procedure: A written visual examination procedure addressing scope, equipment, lighting, surface preparation, acceptance criteria, and documentation requirements must be used. The procedure must be reviewed and accepted by the Owner’s AI.
  • Surface condition: The weld and adjacent base metal must be cleaned of spatter, scale, slag, and other material that would mask discontinuities before examination. For painted or coated pipe, examination must be performed before coating application.
Practical inspector tip: In power plant construction and maintenance, access to the inside surface of large-bore piping for root pass evaluation is common. Always confirm access before designing the welding sequence — if the ID is accessible, incomplete penetration becomes a rejection criterion per 136.4.2, and root grinding or TIG washing may be required to achieve a uniform, full-penetration root. Document access status on the weld traveller.

Paragraph 136.4.2 — Visual Examination Acceptance Criteria in Detail

Paragraph 136.4.2 defines exactly what conditions constitute rejection of a weld after visual examination. The language of the code is explicit: a weld is unacceptable if any of the following conditions are present. There is no provision for engineering critical assessment (ECA) or fitness-for-service evaluation at the initial visual examination stage — rejection criteria are absolute.

ASME B31.1 weld reinforcement limits table from Paragraph 136.4.2 showing maximum external reinforcement by nominal wall thickness
Fig. 1 — ASME B31.1 Paragraph 136.4.2: Weld reinforcement limits table showing maximum permissible external weld reinforcement by nominal pipe wall thickness category.

1. Cracks on the External Surface

Acceptance limit: Zero. Any crack is unacceptable.

All surface-breaking cracks — whether in the weld metal, the heat-affected zone (HAZ), or the adjacent base metal — are unconditionally rejected. This includes crater cracks at the bead termination, transverse weld cracks, longitudinal centreline cracks, HAZ toe cracks, and reheat cracks in Cr-Mo alloys such as P91 and P92. Cracks may appear as fine, dark, linear indications visible under strong raking light, or they may be entirely invisible to the naked eye on initial observation but revealed by liquid penetrant testing. Any suspected crack found during VT must be further investigated by PT or MT before disposition.

For high-alloy power piping materials such as P91 (9Cr-1Mo-V), the risk of hydrogen-induced cold cracking and reheat cracking is significant. Always ensure preheat, interpass temperature control, and post-weld heat treatment are fully compliant with the WPS before attempting VT — a weld examined while still at temperature, before hydrogen has had time to diffuse out, may pass visual examination but fail on subsequent PT. See the P91 welding requirements guide for full preheat and PWHT details.

2. Lack of Fusion on the Surface

Acceptance limit: Zero. Any surface lack of fusion (LOF) is unacceptable.

Surface lack of fusion appears as an unfused interface at the weld toe, between adjacent weld beads, or between the final pass and the base metal. Visually, it presents as a linear groove or seam running parallel to the weld axis at the fusion line, often with a slightly metallic or grainy appearance where the filler has not bonded to the base metal. Surface LOF is invariably accompanied by subsurface LOF extending into the weld cross-section and should be treated as a planar defect requiring complete excavation and rewelding after root cause investigation.

3. Incomplete Penetration (Lack of Penetration)

Acceptance limit: Unacceptable when the inside surface is accessible.

Incomplete penetration (ICP or LOP) means the weld root has not fused completely across the joint root opening, leaving an unfused or partially fused gap at the root. When the inside bore of the pipe is accessible — which it will be for all socket welding preparatory stages and for larger-bore spools where a welder or borescope can enter — ICP is detected by direct visual examination of the root and is an unconditional rejection criterion. When the inside surface is not accessible, ICP cannot be evaluated by VT and must be assessed by RT or UT where required by the examination schedule.

4. Weld Reinforcement Exceeding Specified Limits

Excessive weld reinforcement on butt joints creates a geometric stress concentration at the weld toes that accelerates fatigue crack initiation under cyclic thermal and pressure loading — exactly the loading pattern experienced by power piping. B31.1 therefore sets specific maximum reinforcement limits based on nominal pipe wall thickness:

Nominal Wall Thickness Maximum Weld Reinforcement (External)
Up to 6.4 mm (1/4 in.) 1.6 mm (1/16 in.)
Over 6.4 mm (1/4 in.) to 12.7 mm (1/2 in.) 3.2 mm (1/8 in.)
Over 12.7 mm (1/2 in.) to 25.4 mm (1 in.) 4.0 mm (5/32 in.)
Over 25.4 mm (1 in.) 4.8 mm (3/16 in.)

Weld reinforcement is measured from the plane of the outer pipe surface to the highest point of the weld crown. A weld profile gauge or a straight edge with feeler gauges is used during VT to verify compliance. Weld reinforcement exceeding these limits must be ground down to an acceptable profile before the weld can be accepted. Grinding marks must be smooth and must not reduce the actual wall thickness below the minimum design thickness — verify with an ultrasonic thickness gauge after grinding.

5. Undercut — Circumferential Butt Welds

Acceptance limit: Maximum 0.8 mm (1/32 in.) depth AND must not encroach on minimum required section thickness.

Undercut is a groove or channel melted into the base metal at the weld toe during the welding process. It reduces the effective wall thickness at the most highly stressed location on the weld and creates a notch that concentrates stress under bending, pressure, and thermal loading. For circumferential butt welds in B31.1, undercut is permitted up to a maximum depth of 0.8 mm (1/32 in.), subject to the overriding condition that the remaining wall must meet the minimum required section thickness. Undercut depth is typically measured using a pit gauge or calibrated weld profile gauge.

6. Surface Undercut on Longitudinal Butt Welds

Acceptance limit: Zero. Any surface undercut on longitudinal seam welds is unacceptable.

B31.1 applies a more severe restriction to longitudinal welds than to circumferential welds. This distinction exists because longitudinal seams in power piping experience the full hoop stress from internal pressure — typically twice the axial stress from pressure alone — and any reduction in wall thickness at the seam toe directly reduces pressure-carrying capacity. The code therefore permits no undercut whatsoever on longitudinal butt welds, regardless of depth.

7. Linear Indications

Acceptance limit: Maximum 5 mm (3/16 in.) in length.

Linear indications include any surface-breaking feature with a length-to-width ratio greater than 3:1 — slag tracks, surface LOF seams, surface cracks too fine to clearly identify as cracks, or elongated porosity at the surface. Any linear indication greater than 5 mm (3/16 in.) in its longest dimension is unacceptable. Very short linear indications up to 5 mm may be conditionally accepted, but should be further investigated by PT to confirm they are not cracks, which are unconditionally rejected regardless of length.

8. Surface Porosity

Rejection conditions (either triggers rejection):

  • Any single rounded indication with a maximum dimension greater than 5 mm (3/16 in.)
  • A group of four or more rounded indications separated by 1.5 mm (1/16 in.) or less edge to edge in any direction

Surface porosity is evaluated as rounded indications — those with a length-to-width ratio of 3:1 or less. Individual small pores below 5 mm are accepted provided they do not occur in clusters of four or more at close spacing. The cluster criterion reflects the understanding that closely spaced pores act mechanically as a single larger defect due to ligament thinning between adjacent pores. Gas pores are typically caused by moisture contamination, shielding gas loss, or surface contaminants on the base metal. Persistent porosity during production welding warrants a weld process audit before additional joints are deposited.

9. Arc Strikes Outside the Weld Joint

Acceptance limit: Zero. Any arc strike outside the weld joint area is unacceptable.

An arc strike is a localised area where the welding arc has been initiated on or near the base metal surface outside the intended weld joint. Arc strikes create a small, rapidly quenched heat-affected zone in the base metal characterised by untempered martensite in carbon and low-alloy steels, or by sensitisation in austenitic stainless steels. In Cr-Mo power piping steels (such as P11, P22, P91, and P92), the hardened martensitic zone at an arc strike can initiate hydrogen cracking and, in service, fatigue cracks. All arc strikes must be ground out smooth, inspected by PT or MT, and if the remaining wall is within tolerance, the area may be accepted after NDE confirmation. If grinding reduces the wall below minimum, a repair weld or section replacement is required.

Quick Reference — B31.1 Visual Examination Rejection Summary

The following cards summarise every rejection criterion from Paragraph 136.4.2 at a glance. Use this grid as a field reference during visual examination.

Cracks (External Surface)
Limit: ZERO — any crack, any size,
any location = REJECT
Lack of Fusion (Surface)
Limit: ZERO — any surface LOF
= REJECT
Incomplete Penetration
Limit: ZERO when inside surface
accessible = REJECT
Weld Reinforcement
Limit (mm): ≤6.4t: 1.6 mm
6.4–12.7t: 3.2 mm
12.7–25.4t: 4.0 mm
>25.4t: 4.8 mm
Undercut — Circumferential Welds
Limit: >0.8 mm (1/32 in.) depth
OR encroaches on min. wall = REJECT
Undercut — Longitudinal Welds
Limit: ZERO — any surface
undercut on longitudinal seams = REJECT
Linear Indications
Limit: >5 mm (3/16 in.) length
= REJECT
Surface Porosity
Reject if: single pore >5 mm OR
4+ pores within 1.5 mm edge-to-edge
Arc Strikes
Limit: ZERO — any arc strike
outside weld joint = REJECT

B31.1 vs. B31.3 — Visual Acceptance Criteria Compared

Engineers and inspectors frequently work on projects that include both power piping under B31.1 and process piping under B31.3. Understanding where the two codes diverge is essential to avoid applying the wrong criterion — a common error that results either in unnecessary rework or, more seriously, in welds being accepted that should have been rejected under the applicable code.

Discontinuity Type ASME B31.1 (Power Piping)
Para. 136.4.2
ASME B31.3 (Process Piping)
Normal Fluid Service
Table 341.3.2
Stricter Code
Cracks Zero tolerance Zero tolerance Equal
Lack of Fusion (surface) Zero tolerance Zero tolerance Equal
Incomplete Penetration Zero (when ID accessible) Limited ICP permitted (max 1-1/2 in. in any 6 in.) B31.1 Stricter
Undercut — circumferential max 0.8 mm (1/32 in.) max 1.6 mm (1/16 in.) general; 0.8 mm for alloy steels B31.1 Stricter
Undercut — longitudinal Zero tolerance Same max depth limits as circumferential apply B31.1 Stricter
Weld Reinforcement Tiered by wall thickness (1.6–4.8 mm) Tiered by wall thickness (similar limits) Broadly equivalent
Surface Porosity — single pore max 5 mm (3/16 in.) max 3 mm (1/8 in.) or t/4, whichever less B31.3 Stricter (single pore)
Linear Indications max 5 mm (3/16 in.) max 5 mm (3/16 in.) Equal
Arc Strikes Zero tolerance outside weld joint Zero tolerance Equal
Warning: The above comparison is for general guidance based on the Normal Fluid Service category of B31.3. B31.3 Category M (highly toxic) and High Pressure Fluid Service impose significantly stricter requirements that may exceed even B31.1 limits. Always apply the criteria of the code edition and fluid service category specified in the project engineering design.

Practical Guidance for B31.1 Visual Examination

Pre-Examination Preparation

Surface preparation before VT is not an optional step — it is a prerequisite for a valid examination. Wire brush all spatter from the weld surface and adjacent base metal within at least 25 mm of each weld toe. Remove slag (for SMAW and FCAW processes — less relevant for GTAW and GMAW) completely from the weld crown and toes using a chipping hammer followed by wire brushing. If the examination is performed after PWHT, remove all surface scale by brushing or light grinding. Do not grind the weld profile for cosmetic purposes before VT — if the weld crown appears oversized, measure it before grinding to document the as-deposited condition.

Lighting and Access

Position supplemental lighting at a low angle of incidence (raking light) across the weld surface to enhance the shadow contrast of surface discontinuities. Small, shallow undercut and fine surface cracks become far more visible under raking light than under diffuse overhead illumination. Use a weld profile gauge or straight edge to confirm reinforcement measurements rather than relying on visual estimation — gauges are inexpensive, quick to use, and produce a documentable measurement.

Documentation Requirements

While ASME B31.1 states that records of individual visual examinations are not always mandatory (except for in-process examination), sound quality practice dictates that VT results are recorded on the weld traveller or inspection record card for every weld. Record: weld identification number, examination date, examiner name and qualification, surface condition, any indications found and their disposition (accepted or rejected), and any corrective action taken. This record is required by most Quality Programmes operating under ASME and by power utility Owner requirements.

Inspector qualifications: ASME B31.1 visual examiners are typically required to hold ANST SNT-TC-1A Level II or equivalent qualification in VT by project quality plans. The Authorised Inspector (AI) performing code inspection is typically employed by an ASME-accredited inspection body. Do not confuse the examiner (fabricator’s personnel) with the inspector (Owner’s AI) — both have defined roles under Chapter VI.

Repair Sequence for Rejected Welds

All rejected welds under B31.1 must follow a documented repair sequence before re-examination. The general sequence is: (1) map and document the location and character of each rejection, (2) identify the root cause before excavating (root cause determines the corrective action), (3) excavate by grinding, arc gouging, or machining to sound metal, extending 25 mm beyond the apparent limits of each discontinuity, (4) inspect the excavation by PT or MT to confirm removal to sound metal, (5) pre-heat if required by material and WPS, (6) re-weld using a qualified repair WPS, (7) perform PWHT if required, (8) re-examine by VT and any additionally required NDE method. For mechanical test requirements on production weld samples, see the WeldFabWorld mechanical testing guide.

NDE Methods Required in Addition to Visual Examination Under B31.1

Visual examination is the baseline but is not the sole NDE requirement for all B31.1 welds. Table 136.4 specifies when additional NDE is required. Passing VT does not guarantee that a weld is free of subsurface discontinuities — RT and UT are required for that assurance on welds meeting the pressure/temperature threshold.

NDE Method Standard Scope in B31.1 What It Detects (Beyond VT)
Radiographic Testing (RT) ASME Section V Art. 2 100% for high-pressure/high-temp welds per Table 136.4 Subsurface porosity, slag, LOP, LOF, cracks
Ultrasonic Testing (UT) ASME Section V Art. 4/5 Alternative to RT where geometry precludes RT; project-specified Planar defects, LOF, cracks in thick sections
Liquid Penetrant (PT) ASME Section V Art. 6 Not required by B31.1 Table 136.4 alone; specified for PWHT verification, arc strikes Surface and near-surface cracks, fine LOF seams
Magnetic Particle (MT) ASME Section V Art. 7 Ferromagnetic materials only; project-specified or as repair verification Surface and near-surface cracks, sub-surface defects to ~3 mm depth

For comprehensive guidance on all NDE methods applicable to power piping inspection, refer to the WeldFabWorld mechanical and non-destructive testing guide. For understanding how weld procedure and welder qualifications underpin the examination programme, the ASME Section IX practice quiz is an excellent self-assessment resource.

Recommended References for B31.1 Visual Examination

ASME B31.1 Power Piping Code
The primary code governing all aspects of power piping design, fabrication, examination, and testing. Essential for anyone working on boiler and turbine piping systems.
View on Amazon
AWS Welding Inspection Handbook
The definitive CWI reference covering visual inspection procedures, NDE methods, weld defect evaluation, and acceptance criteria across AWS and ASME codes.
View on Amazon
ASME Section V — NDE Methods
ASME Boiler and Pressure Vessel Code Section V covers all NDE methods referenced by B31.1, including Article 9 for visual examination procedures.
View on Amazon
Weld Inspection Gauges Set
Professional weld gauge set for measuring reinforcement height, undercut depth, fillet size, and weld angles — essential for accurate B31.1 visual examination.
View on Amazon

Disclosure: WeldFabWorld participates in the Amazon Associates programme (StoreID: neha0fe8-21). If you purchase through these links, we may earn a small commission at no extra cost to you. This helps support free technical content on this site.

Frequently Asked Questions — ASME B31.1 Visual Examination

What paragraph of ASME B31.1 covers visual examination acceptance criteria?
Visual examination acceptance criteria for power piping welds are specified in Paragraph 136.4.2 of ASME B31.1. This paragraph falls within Chapter VI of the code, titled “Inspection, Examination, and Testing,” and defines what constitutes an unacceptable weld condition after visual examination of the completed weld. The visual examination method itself must follow ASME BPVC Section V, Article 9, which sets out procedural requirements including minimum illumination, examiner distance, and optical aid usage.
Is any level of undercut acceptable under ASME B31.1?
ASME B31.1 Paragraph 136.4.2 permits undercut up to a maximum depth of 0.8 mm (1/32 in.) on circumferential butt welds, provided the depth does not encroach on the minimum required section thickness. Any undercut that reduces the remaining wall below the minimum design thickness is unacceptable regardless of its absolute depth. Importantly, all surface undercut on longitudinal butt welds is unacceptable — there is no tolerance permitted for longitudinal seam undercut, reflecting the higher hoop stress loading carried by longitudinal seams in pressure piping.
Does ASME B31.1 allow any incomplete penetration?
Under ASME B31.1, incomplete penetration (also called lack of penetration) is considered unacceptable when the inside surface of the weld joint is accessible for inspection. If the inside surface is not accessible, incomplete penetration cannot be evaluated by visual examination and must be assessed by volumetric NDE methods such as radiography or ultrasonic testing as required by the applicable examination schedule. B31.1 takes a stricter stance on incomplete penetration than B31.3 Normal Fluid Service, reflecting the high-pressure, high-temperature service conditions typical of power piping.
What are the weld reinforcement limits in ASME B31.1?
ASME B31.1 specifies maximum weld reinforcement limits based on the nominal pipe wall thickness: up to 6.4 mm (1/4 in.) wall — max 1.6 mm (1/16 in.); 6.4 to 12.7 mm — max 3.2 mm (1/8 in.); 12.7 to 25.4 mm — max 4.0 mm (5/32 in.); over 25.4 mm — max 4.8 mm (3/16 in.). These limits apply to external weld reinforcement on butt joints and control the stress concentration at the weld toes. If reinforcement exceeds the limit, it must be ground back to an acceptable profile and the remaining wall confirmed by ultrasonic thickness measurement.
How does B31.1 visual examination differ from B31.3?
ASME B31.1 (Power Piping) applies stricter visual examination criteria than B31.3 Normal Fluid Service because power piping systems operate under severe sustained conditions — elevated temperature, high pressure, and cyclic thermal loading. B31.1 permits zero surface undercut on longitudinal welds and a tighter undercut limit of 0.8 mm on circumferential welds compared to B31.3’s 1.6 mm general limit. B31.1 also rejects all incomplete penetration when the ID is accessible, whereas B31.3 Normal allows limited ICP. Projects with both power and process piping must clearly identify which code governs each system and ensure inspection criteria are not interchanged.
What is the surface porosity acceptance limit under ASME B31.1?
ASME B31.1 Paragraph 136.4.2 rejects surface porosity under two conditions: (1) any single rounded indication with a dimension greater than 5 mm (3/16 in.), or (2) a cluster of four or more rounded indications separated by 1.5 mm (1/16 in.) or less edge to edge in any direction. Individual pores below 5 mm are accepted provided they do not occur in clusters of four or more at close spacing. Persistent surface porosity during production welding should trigger a weld process audit to identify and correct the underlying cause — typically moisture in consumables, shielding gas loss, or surface contamination.
Are arc strikes outside the weld joint acceptable in B31.1 power piping?
No. ASME B31.1 explicitly rejects arc strikes outside the weld joint area. Arc strikes cause local hardening of the base metal heat-affected zone, creating notch-like stress concentrators that can initiate fatigue or stress corrosion cracks in service. In high-temperature power piping — particularly in P91 and P92 creep-resistant alloys — arc strikes are especially damaging because they produce brittle untempered martensite. Repair requires controlled grinding, PT inspection, and potentially local PWHT. See the P91 welding guide for preheat and PWHT requirements on Cr-Mo power piping.
Who is qualified to perform visual examination under ASME B31.1?
ASME B31.1 does not itself prescribe specific personnel qualification levels for visual examination, but requires that examiners have demonstrated competency and understand the acceptance criteria of Paragraph 136.4.2. In practice, power generation projects typically require visual examiners to hold ASNT Level II or equivalent qualification in VT per SNT-TC-1A or CP-189. Third-party inspection by an Authorised Inspector (AI) is required for code-stamped B31.1 systems. The Authorised Inspector is employed by an ASME-accredited inspection body and exercises oversight of the entire examination programme, not just individual weld examinations.

Related Technical Resources on WeldFabWorld

Related Articles

ASME Codes & Standards Cast Iron Welding Consumables: What ASME SFA-5.15 (Revised 2025) Actually Requires
ASME Codes & Standards Conditions for Exemption from Impact Testing as per ASME Section VIII Div. 1
ASME Codes & Standards How to Prepare a WPS and PQR: Fabricator Shall Know
ASME Codes & Standards Weld Joint Strength Reduction Factor (W) — ASME B31.3 Code Perspective with calculator